6 dnpnet.config.dnp_server_override – ProSoft Technology MVI56E-DNPNET User Manual
Page 36

Contents
MVI56E-DNPNET ♦ ControlLogix Platform
User Manual
DNPNET Ethernet Client/Server Communication Module
Page 36 of 140
ProSoft Technology, Inc.
February 13, 2015
Tag Name
Range
Description
DNPNET.CONFIG.DNP3_Clie
nt.Only_Time_Sync_Servers_I
f_Synced
0 or 1
This parameter determines if the client will
send a time sync message to servers when its
own time has not yet been synced via PLC or
a connected client. If set to 0, the client will
send a time sync to connected servers even if
its own clock has not been synced by the PLC
or another connected client. If set to 1, the
client will not send time syncs to servers until it
has been synced by the PLC or a connected
client.
DNPNET.CONFIG.DNP3_Clie
nt.Use_Binary_Output_status_
Data
0 or 1
Enable database and functions for reading the
status of Binary Outputs (object 10).
DNPNET.CONFIG.DNP3_Clie
nt.Use_Analog_Output_status
_Data
0 or 1
Enable database and functions for reading the
status of Analog Outputs (object 40).
DNPNET.CONFIG.DNP3_Clie
nt.Dont_Process_IIN
0 or 1
By default (0), the Client module will
automatically make requests to servers that
have IIN bits set for class data, need time,
restart, or buffer overflow until these IIN bits
have been cleared. If this parameter is set to
1, the Client will NOT automatically make
these requests as a result of these IIN bits
being set.
DNPNET.CONFIG.DNP3_Clie
nt.reserved_0
-
-
2.3.6 DNPNET.CONFIG.DNP_Server_Override
Assigns Class and Deadband overrides to individual point types. You can adjust the size of
each of the 5 point type arrays.
Tag Name
Range
Description
DNPNET.CONFIG.DNP_Serv
er_Override.Binary_Inputs.
n/a
Number of binary input words contained in the
IED database to be transferred to the PLC and
obtained from the attached IED units.
This array size ranges from 0 to 1000.
Point_Number
0 to Number of
points configured
Point number
index to be
overridden
Point number index to be overridden
Class
1 to 3
Class number assigned to point number
specified above
DNPNET.CONFIG.DNP_Serv
er_Override.Analog16_Inputs.
n/a
Number of 16-bit analog input points contained
in the IED database to be transferred to the
PLC and obtained from the attached IED units.
This array size ranges from 0 to 1000.
Point_Number
0 to Number of
points configured
Point number index to be overridden