ProSoft Technology MVI56E-DNPNET User Manual
Page 131

MVI56E-DNPNET ♦ ControlLogix Platform
Contents
DNPNET Ethernet Client/Server Communication Module
User Manual
ProSoft Technology, Inc.
Page 131 of 140
February 13, 2015
OBJECT
REQUEST
RESPONSE
Obj Var Description
Func
Codes
Qual
Codes
(hex)
Func
Codes
Qual
Codes
(hex)
Data
Size
(bits)
NOTES
8
16-Bit Delta Counter
Without Flag
129,
130
00, 01
16
Client will process this
variation
21 0
Frozen Counter - All
Variations
1
06
32
Client will generate this
variation
1
32-Bit Frozen Counter
129,
130
00, 01
40
Client will process this
variation
2
16-Bit Frozen Counter
129,
130
00, 01
24
Client will process this
variation
3
32-Bit Frozen Delta
Counter
40
4
16-Bit Frozen Delta
Counter
24
5
32-Bit Frozen Counter
With Time Of Freeze
88
6
16-Bit Frozen Counter
With Time Of Freeze
72
7
32-Bit Frozen Delta
Counter With Time Of
Freeze
88
8
16-Bit Frozen Delta
Counter With Time Of
Freeze
72
9
32-Bit Frozen Counter
Without Flag
1
06
129,
130
00, 01
32
Client will generate and
process this variation
10 16-Bit Frozen Counter
Without Flag
1
06
129,
130
00, 01
16
Client will generate and
process this variation
11 32-Bit Frozen Delta
Counter Without Flag
32
12 16-Bit Frozen Delta
Counter Without Flag
16
22 0
Counter Change Event
- All Variations
1
06, 07,
08
Client will not generate a
request for this variation
1
32-Bit Counter Change
Event Without Time
129,
130
17, 28
40
Client will process this
variation
2
16-Bit Counter Change
Event Without Time
129,
130
17, 28
24
Client will process this
variation
3
32-Bit Delta Counter
Change Event Without
Time
40
4
16-Bit Delta Counter
Change Event Without
Time
24
5
32-Bit Counter Change
Event With Time
88
6
16-Bit Counter Change
Event With Time
72