MVI56E-MNETCR ♦ ControlLogix Platform

Reference

Modbus TCP/IP Multi Client Enhanced Communications Module for Remote Chassis

User Manual

ProSoft Technology, Inc.

Page 99 of 159

June 14, 2011

Data contained in this database is paged through the input and output images by
coordination of the ControlLogix ladder logic and the MVI56E-MNETCR module's
program. Up to 40 words of data can be transferred from the module to the
processor at a time. Up to 40 words of data can be transferred from the
processor to the module. Each image has a defined structure depending on the
data content and the function of the data transfer. The module uses the following
block numbers:

Block Range

Descriptions

-1

Null block

0

Null block

1 to 125

Read or write data

1000 to 1124

Output Initialization Blocks

2000 to 2029

Event Command Block (page 103)

3000 to 3029

Client status request/response blocks (page 105)

5001 to 5016

Command Control (page 106, page 102)

9990

Set new module IP address (page 107)

9991

Get module IP address

9998

Warm-boot control block (page 109)

9999

Cold-boot control block

These block identification codes can be broken down into a few groups: Normal
data transfer blocks (-1 to 125), Initialization blocks (1000 to 1124), and
Command control blocks (2000, 5000 to 5016, 9998 and 9999).