Diagnostics and Troubleshooting

MVI56E-MNETCR ♦ ControlLogix Platform

User Manual

Modbus TCP/IP Multi Client Enhanced Communications Module for Remote Chassis

Page 80 of 159

ProSoft Technology, Inc.

June 14, 2011

4.1

LED Status Indicators

4.1.1 Scrolling LED Status Indicators

The scrolling LED display indicates the module's operating status as follows:

Initialization Messages

Code

Message

Boot / DDOK

Module is initializing

Ladd

Module is waiting for required module configuration data from
ladder logic to configure the application port(s)

Waiting for Processor Connection

Module did not connect to processor during initialization

Sample ladder logic or AOI is not loaded on processor

Module is located in a different slot than the one
configured in the ladder logic/AOI

Processor is not in RUN or REM RUN mode

Last config:

Indicates the last date when the module changed its IP
address. You can update the module date and time through
the module’s web page, or with the Optional MVI56E Add-On
Instruction.

After power up and every reconfiguration, the module will
display the configuration of the application port(s). The
information consists of:
Client

C0 C2 C3 C4 ….. C29

Operation Messages
After the initialization step, the following message pattern will be repeated.

Code

Message

OK: Module is communicating with processor
ERR: Module is unable to communicate with processor. For
this scenario, the message above is replaced
with "Processor faulted or is in program mode".

Module IP address

OK: Port is communicating without error
Communication Errors: port is having communication errors.
Refer to PCB diagnostics (page 79) for further information
about the error.