ProSoft Technology MVI56E-MNETCR User Manual
Page 143

MVI56E-MNETCR ♦ ControlLogix Platform
Reference
Modbus TCP/IP Multi Client Enhanced Communications Module for Remote Chassis
User Manual
ProSoft Technology, Inc.
Page 143 of 159
June 14, 2011
Select the
1756-M
ODULE
(Generic 1756 Module) from the list and click OK.
This action opens the N
EW
M
ODULE
dialog box.
Parameter
Value
Name
Enter a module identification string. The recommended value is
MNETCR.
Description
Enter a description for the module. Example: Modbus TCP/IP
Multi Client Enhanced Communications Module for Remote
Chassis.
Comm Format
Select D
ATA
-INT
(Very Important)
Slot
Enter the slot number in the rack where the MVI56E-MNETCR
module will be installed.
Input Assembly Instance
1
Input Size
42
Output Assembly Instance
2
Output Size
42
Configuration Assembly Instance 4
Configuration Size
0
Enter the Name, Description and Slot options for your application. You must
select the C
OMM
F
ORMAT AS
D
ATA
-
INT in the dialog box, otherwise the
module will not communicate over the backplane of the ControlLogix rack.