MVI56E-MNETCR ♦ ControlLogix Platform

Reference

Modbus TCP/IP Multi Client Enhanced Communications Module for Remote Chassis

User Manual

ProSoft Technology, Inc.

Page 139 of 159

June 14, 2011

5.6.5 Writing the Ethernet Settings to the Module

Expand the MVI56EMNETCRETHERNET

controller tag.

Set the new Ethernet configuration in MVI56EMNETCRETHERNET.C

ONFIG

Move a value of 1 to MVI56EMNETCRETHERNET.W

RITE

After the message is executed, the MVI56EMNETCRETHERNET.W

RITE

bit

resets to 0.

To check the status of the message, refer to the WRITEETHERNETMSG

tag.