MVI56E-MNETCR ♦ ControlLogix Platform

Start Here

Modbus TCP/IP Multi Client Enhanced Communications Module for Remote Chassis

User Manual

ProSoft Technology, Inc.

Page 29 of 159

June 14, 2011

Create the Module - Remote Rack
1 In the C

ONTROLLER

O

RGANIZATION

window, select the remote 1756

B

ACKPLANE

node, and then click the right mouse button to open a shortcut

menu. On the shortcut menu, choose N

EW

M

ODULE

.

2 This action opens the S

ELECT

M

ODULE

dialog box. Expand the O

THER

node,

and then select 1756-MODULE

(G

ENERIC

1756

M

ODULE

)

3 Set the Module Properties values as follows:

Parameter

Value

Name

Enter a module identification string. The recommended value is
MNETCR.

Description

Enter a description for the module. Example: Modbus TCP/IP
Multi Client Enhanced Communications Module for Remote
Chassis.

Comm Format

Select D

ATA

-INT

(Very Important)

Slot

Enter the slot number in the rack where the MVI56E-MNETCR
module will be installed.

Input Assembly Instance

1

Input Size

42

Output Assembly Instance

2

Output Size

42

Configuration Assembly Instance 4

Configuration Size

0