Page 29

MVI56E-MNETCR ♦ ControlLogix Platform
Start Here
Modbus TCP/IP Multi Client Enhanced Communications Module for Remote Chassis
User Manual
ProSoft Technology, Inc.
Page 29 of 159
June 14, 2011
Create the Module - Remote Rack
1 In the C
ONTROLLER
O
RGANIZATION
window, select the remote 1756
B
ACKPLANE
node, and then click the right mouse button to open a shortcut
menu. On the shortcut menu, choose N
EW
M
ODULE
.
2 This action opens the S
ELECT
M
ODULE
dialog box. Expand the O
THER
node,
and then select 1756-MODULE
(G
ENERIC
1756
M
ODULE
)
3 Set the Module Properties values as follows:
Parameter
Value
Name
Enter a module identification string. The recommended value is
MNETCR.
Description
Enter a description for the module. Example: Modbus TCP/IP
Multi Client Enhanced Communications Module for Remote
Chassis.
Comm Format
Select D
ATA
-INT
(Very Important)
Slot
Enter the slot number in the rack where the MVI56E-MNETCR
module will be installed.
Input Assembly Instance
1
Input Size
42
Output Assembly Instance
2
Output Size
42
Configuration Assembly Instance 4
Configuration Size
0