Cold Boot Block (9999)
This block is equivalent to performing a hardware reset, and causes the module
to restart in the same way as if the power was cycled. The Cold Boot control
block also reloads the module's backplane and application port drivers, restarts
the program, and resets all internal registers to zero.

Note: In some cases, the read section of the module database (transferred from module to
processor) must keep its values after a reboot. To repopulate the module's registers with the last
values the module sent to the processor, set the I

NITIALIZE

O

UTPUT

D

ATA

parameter in the module

configuration to Y

ES

.


The following table describes the format of the control block.

Offset

Description

Length

0

9999

1

1 to 41

Spare

41


The module does not send a response block for this command.