ProSoft Technology MVI56E-MNETCR User Manual
Page 56

Configuring the MVI56E-MNETCR Module
MVI56E-MNETCR ♦ ControlLogix Platform
User Manual
Modbus TCP/IP Multi Client Enhanced Communications Module for Remote Chassis
Page 56 of 159
ProSoft Technology, Inc.
June 14, 2011
Command list example:
Enable
N
O
(0) or Y
ES
(1)
This field defines whether or not the command is to be executed.
Value
Description
N
O
(0)
The command is disabled and will not be executed in the normal polling sequence.
Y
ES
(1)
The command is executed each scan of the command list if the Poll Interval Time is
set to zero. If the Poll Interval time is set, the command will be executed when the
interval timer expires.
Internal Address
0 to 4999 (for word-level addressing)
or
0 to 65535 (for bit-level addressing)
This field specifies the database address in the module's internal database to use
as the destination for data brought in by a read command or as the source for
data to be sent out by a write command. The database address is interpreted as
a bit address or a 16-bit word (register) address, depending on the Modbus
Function Code used in the command.
For Modbus functions 1, 2, 5, and 15, this parameter is interpreted as a bit-
level address.
For Modbus functions 3, 4, 6, and 16, this parameter is interpreted as a word-
or register-level address.