beautypg.com

ProSoft Technology MVI56E-MNETCR User Manual

Page 76

background image

Ladder Logic

MVI56E-MNETCR ♦ ControlLogix Platform

User Manual

Modbus TCP/IP Multi Client Enhanced Communications Module for Remote Chassis

Page 76 of 159

ProSoft Technology, Inc.

June 14, 2011

Block Statistics Object (MNETCRBLOCKSTATS)
This object contains a structure that includes the status information for the data
transfer operations between the processor and the module. The following table
describes the structure of this object.

Name

Data Type

Description

Read

INT

Total number of read block transfers

Write

INT

Total number of write block transfers

Parse

INT

Total number of blocks parsed

Event

INT

Total number of event blocks received

Cmd

INT

Total number of command blocks received

Err

INT

Total number of block transfer errors

Client Statistics Object (MNETCRCLIENTSTATS)
This block also contains a structure that includes Client statistics. The following
table describes the structure of this object.

Name

Data Type

Description

CmdReq

INT

Total number of command list requests sent

CmdResp

INT

Total number of command list responses received

CmdErr

INT

Total number of command list errors

Requests

INT

Total number of requests for port

Responses

INT

Total number of responses for port

ErrSent

INT

Total number of errors sent

ErrRec

INT

Total number of errors received

CfgErrWord

INT

Configuration Error Word

CurErr

INT

Current Error code

LastErr

INT

Last recorded error code

Refer to MVI56E-MNETCR Status Data Definition (page 105, page 112) for a