Create the Module - Local Rack
1 In the C

ONTROLLER

O

RGANIZATION

window, expand the I/O configuration

node.

2 Select the 1756

B

ACKPLANE

node, and then click the right mouse button to

open a shortcut menu. On the shortcut menu, choose N

EW

M

ODULE

...

3 This action opens the S

ELECT

M

ODULE

dialog box.

4 Select the 1756-M

ODULE

(G

ENERIC

1756

M

ODULE

)

from the list and click OK.

5 Set the Module Properties values as follows:

Parameter

Value

Name

Enter a module identification string. The recommended value is
MNETCR.

Description

Enter a description for the module. Example: Modbus TCP/IP
Multi Client Enhanced Communications Module for Remote
Chassis.

Comm Format

Select D

ATA

-INT

(Very Important)

Slot

Enter the slot number in the rack where the MVI56E-MNETCR
module is to be installed.

Input Assembly Instance

1

Input Size

42

Output Assembly Instance

2

Output Size

42

Configuration Assembly Instance 4

Configuration Size

0