beautypg.com

ProSoft Technology MVI56E-MNETCR User Manual

Page 95

background image

MVI56E-MNETCR ♦ ControlLogix Platform

Reference

Modbus TCP/IP Multi Client Enhanced Communications Module for Remote Chassis

User Manual

ProSoft Technology, Inc.

Page 95 of 159

June 14, 2011

Modbus TCP/IP Client (Master)
The MVI56E-MNETCR is a Client-only module that will operate on a local or
remote rack. This module was created to improve performance when controlling
multiple servers on a Modbus TCP/IP network. The module supports up to 30
Clients with up to 16 commands for each Client.
Actively reads data from and writes data to Modbus TCP/IP devices, using

MBAP or Encapsulated Modbus message formats

Transmits Modbus Function Codes 1, 2, 3, 4, 5, 6, 7, 15, and 16
Offers 30 Client connections with up to 16 commands each to talk to multiple

servers

ControlLogix processor can be programmed to use special functions to

control the activity on the Client by actively selecting commands to execute
from the command list (Command Control) or by issuing commands directly
from the ladder logic (Event Commands)

5.1.2 Functional Specifications

Modbus data types overlap in the module's memory database, so the same

data can be conveniently read or written as bit-level or register-level data.

Configurable floating point data movement is supported, including support for

Enron or Daniel

®

floating point formats

Special functions (Command Control, Event Commands, status, etc.) are

supported by message transfer (unscheduled) using the MSG instruction

Configurable parameters for the Client including a minimum response delay

of 0 to 65535 ms and floating point support

Supports up to 30 Clients with up to 16 commands for each Client
Error codes, counters, and module status available from module memory

through the Clients, or through the ladder logic and controller tags in
RSLogix 5000