ProSoft Technology MVI56E-MNETCR User Manual
Page 37

MVI56E-MNETCR ♦ ControlLogix Platform
Start Here
Modbus TCP/IP Multi Client Enhanced Communications Module for Remote Chassis
User Manual
ProSoft Technology, Inc.
Page 37 of 159
June 14, 2011
Adding Multiple Modules (Optional)
Important: If your application requires more than one MVI56E-MNETCR module into the same
project, follow the steps below.
1 In the I/O
C
ONFIGURATION
folder, click the right mouse button to open a
shortcut menu, and then choose N
EW
M
ODULE
.
2 Select 1756-MODULE
3 Fill the module properties as follows:
Parameter
Value
Name
Enter a module identification string. Example: MNETCR_2.
Description
Enter a description for the module. Example: Modbus TCP/IP
Multi Client Enhanced Communications Module for Remote
Chassis
Comm Format
Select D
ATA
-INT.
Slot
Enter the slot number in the rack where the MVI56E-
MNETCR module is located.
Input Assembly Instance
1
Input Size
42
Output Assembly Instance
2
Output Size
42
Configuration Assembly Instance
4
Configuration Size
0