Start Here

MVI56E-MNETCR ♦ ControlLogix Platform

User Manual

Modbus TCP/IP Multi Client Enhanced Communications Module for Remote Chassis

Page 22 of 159

ProSoft Technology, Inc.

June 14, 2011

5 The module’s default IP address is 192.168.0.250.

6 Choose an unused IP within your subnet, and then click OK.

1.8.1 Using CIPconnect to Connect to the Module

You can use CIPconnect

®

to connect a PC to the MVI56E-MNETCR module over

Ethernet using Rockwell Automation’s 1756-ENBT EtherNet/IP

®

module. This

allows you to configure the MVI56E-MNETCR module and network, upload and
download files, and view network and module diagnostics from a PC. RSLinx is
not required when you use CIPconnect. All you need are:
The IP addresses and slot numbers of any 1756-ENBT modules in the path
The ControlNet node numbers and slot numbers of any 1756-CNBx

ControlNet Bridge modules in the path

The slot number of the MVI56E-MNETCR in the destination ControlLogix

chassis (the last ENBT/CNBx and chassis in the path).

To use CIPconnect, follow these steps.
1 In the Select Connection Type dropdown list, choose 1756-ENBT. The

default path appears in the text box, as shown in the following illustration.