ProSoft Technology MVI69-FLN User Manual
Page 95

Reference MVI69-FLN
♦ CompactLogix Platform
FA Control Network Communication Module
ProSoft Technology, Inc.
Page 95 of 137
November 3, 2008
You can monitor the FA Link Status through the
FLNETSTATUS.Own_node.FA_link_status. For this example bit 0 is currently set
as 0 (MVI69-FLN is in-ring)
Setting a value of 1 to FLNETMODULE.CONTROL.In_Out_RingCommand
controller tag will set the MVI69-FLN module as out-ring:
The out-ring state can be checked by the FA Link status which now indicates that
all bits are set to 0 (out-ring).
You can observe that the LER/LE LED will be asserted to indicate that the
module was set out-ring.
Setting a value of 2 to FLNETMODULE.CONTROL.In_Out_RingCommand
controller tag will set the MVI69-FLN module again to in-ring:
The in-ring state can be checked by the FA Link status which now indicates that
bit 0 is set to 1 (in-ring)
You can observe that the LED display will have an "I" and the word "OK".
Self-node status
This is the information on self-node status to be given to the upper layer.
Message Description
Self-node number conflict
Indicates the management information on node number
conflicted to see whether any node having the same node
number as the self-node setting exists on the network or not.
Token monitoring time error
Indicates the error notice information that transmit processing
has not been completed within the token monitoring time set in
the self-node.
Receive waiting status
Indicates that no frame has been received at network
initialization, being a frame receive waiting status.
Initialize error
Indicates an error is found in an initial setting or resetting
parameter.