ProSoft Technology MVI69-FLN User Manual
Page 18

MVI69-FLN ♦ CompactLogix Platform
Start Here
FA Control Network Communication Module
Page 18 of 137
ProSoft Technology, Inc.
November 3, 2008
This action opens the Select Module Type dialog box.
Select the 1769-Module (Generic 1769 Module) from the list and click OK.
You should configure the Connection Parameters according to the Block Transfer
Size parameter in the configuration file as follows:
On the General page, fill in the values shown in the following tables, according to
the Block Transfer Size parameter in the configuration file. You must select the
Comm Format as Data - INT.
The configured Input Size and Output Size will depend on the block transfer size
parameter defined in the configuration file. Use the values in the table
corresponding with the block transfer size you configured.
Block Transfer Size = 240
Field Recommended
Value
Type
1769-MODULE Generic 1769 Module
Parent Local
Name MVI69
Description
MVI69 Application Module
Comm Format
Data - INT
Slot
The slot number in the rack where the module is installed
Input Assembly
Instance
101
Input Size
242
Output Assembly
Instance
100
Output Size
244
Configuration
Assembly Instance
102
Configuration Size
0