3.8
Communications Management Tables
Node status is managed using three types of management tables: Own node
management tables, participating node management tables, and network
management
3.8.1 Own Node Management Table
The own node management table manages the local node settings.
Item
Bytes
Contents (data range)
Node number
1 byte
1 to 249
Common Memory Area 1 first word
2 bytes
Word address (0 to 0xff)
Common Memory Area 1 data size
2 bytes
Size (0 to 0x200)
Common Memory Area 2 first word
2 bytes
Word address (0 to 0x2000)
Common Memory Area 2 data size
2 bytes
Size (0 to 0x200)
Upper layer status
2 bytes
RUN / STOP / ALARM / WARNING /
NORMAL
Token monitoring time
1 byte
Unit: 1 ms
Minimum allowable frame interval
1 byte
Unit: 100 _s
Vendor code
10 bytes
Vendor code
Manufacturer model
10 bytes
Manufacturer model, device name
Node name (equipment name)
10 bytes
User-defined node name
Protocol version
1 byte
0x80 (fixed)
FA link status
1 byte
Participating, not participating, etc.
Local node status
1 byte
Duplicate node number detection, etc.
3.8.2 Participating Node Management Table
The participating node management table manages information on the nodes in
the network.
Item
Bytes
Contents (data range)
Node number
1 byte
1 to 254 if participating (a zero in this
field for a node indicates the node is
not participating on the network)
Upper layer status
2 bytes
RUN / STOP / ALARM / WARNING /
NORMAL
Common Memory Area 1 data first word 2 bytes
Word address (0 to 0x1ff)
Common Memory Area 1 data size
2 bytes
Size (0 to 0x200)
Common Memory Area 2 data first word 2 bytes
Word address (0 to 0x1fff)
Common Memory Area 2 data size
2 bytes
Size (0 to 0x2000)
Minimum allowable refresh cycle time
2 bytes
Unit: 1 ms
Token monitoring time
1 byte
Unit: 1 ms
Minimum allowable frame interval
1 byte
Unit: 100 ms
Link status
1 byte
Participating, not participating, etc.