beautypg.com

E 20) – ProSoft Technology MVI69-FLN User Manual

Page 20

background image

MVI69-FLN ♦ CompactLogix Platform

Start Here

FA Control Network Communication Module

Page 20 of 137

ProSoft Technology, Inc.

November 3, 2008

1.6.1 Sample Ladder Logic

Important: You must download the sample ladder to the CompactLogix processor, otherwise the
module will be unable to establish communication with the processor.
If you see the message

"Waiting for connection to processor..."

when you connect to the configuration/debug port on the MVI69-FLN module using HyperTerminal,
connect to the processor with RSLogix and download the sample ladder logic to the processor
before continuing.

Open the Sample Ladder Logic in RSLogix

The sample program for your MVI69-FLN module includes custom tags, data
types and ladder logic for data I/O, status and monitoring. For most applications,
you can run the sample ladder program without modification, or, for advanced
applications, you can incorporate the sample program into your existing
application.

Important: The RSLinx service must be installed and running on your computer in order for
RSLogix to communicate with the processor. Refer to your RSLinx and RSLogix documentation for
help configuring and troubleshooting these applications.

To open the sample program

1 Connect an RS-232 serial cable from the COM (serial) port on your PC to the

communication port on the front of the processor.

2 Start RSLogix 5000 and close any existing project that may be loaded.
3 Open the Communications menu and choose Go Online. RSLogix will

establish communication with the processor. This may take a few moments.

4 When RSLogix has established communication with the processor, the

Connected To Go Online dialog box will open.

5 On the Connected to Go Online dialog box, click the Select File button.
6 Choose the sample program file, and then click the Select button.
7 RSLogix will load the sample program.

Next, configure the correct controller type and slot number for your application.

Download the Sample Program to the Processor

To download the sample program from RSLogix 5000 to the CompactLogix processor:

Note: The key switch on the front of the CompactLogix module must be in the REM position.

1 If you are not already online to the processor, open the Communications

menu, and then choose Download. RSLogix will establish communication
with the processor.

2 When communication is established, RSLogix will open a confirmation dialog

box. Click the Download button to transfer the sample program to the
processor.

3 RSLogix will compile the program and transfer it to the processor. This

process may take a few minutes.