MVI69-FLN ♦ CompactLogix Platform

Start Here

FA Control Network Communication Module

Page 34 of 137

ProSoft Technology, Inc.

November 3, 2008

1.12.2 Setting the Mapping Parameters

To set mapping parameters

1 Enable the Use BP Map Table parameter with a value of Y as follows:

Use BP Map Table : Y #Use BP mapping (Y=Use maps, N=Don't use maps

(default))

2 Setup the mapping for your application through the [FL-NET BACKPLANE

MAPPING] section of the configuration file.

Where each parameter is defined as follows:

Parameter Description

Node Node

number

A1 Network Start

Start word offset in the node area (within the network common
memory) to be mapped into the virtual backplane map. This is not the
absolute offset within the common memory. For example, if the node
top address is 200 (size of 150 words), in order to remap the last 50
words of that node then enter a A1 Network Start value of 100 (not
300).

A1 Network Size

Total number of words (starting from A1 Network Start offset) to be
mapped into the virtual backplane map.

A1 Network Backplane
Start

Start absolute word offset in the virtual backplane map where the
mapped A1 data will be copied to.

A2 Network Start

Start word offset in the node area (within the network common
memory) to be mapped into the virtual backplane map. This is not the
absolute offset within the common memory. For example, if the node
top address is 200 (size of 150 words), in order to remap the last 50
words of that node then enter a A2 Network Start value of 100 (not
300).

A2 Network Size

Total number of words (starting from A2 Network Start offset) to be
mapped into the virtual backplane map.

A2 Network Backplane
Start

Start absolute word offset in the virtual backplane map where the
mapped A2 data will be copied to.

3 Setup the portion of the virtual backplane map to be transferred to the

processor.

BP Area 1 Top : 0 #0...511 top address for area 1

BP Area 1 Size : 200 #0...512 area 1 data size in words

BP Area 2 Top : 0 #0...8191 top address for area 2

BP Area 2 Size : 200 #0...8192 area 2 data size in words

The following example shows how to use the map feature by configuring the