MVI69-FLN ♦ CompactLogix Platform

Diagnostics and Troubleshooting

FA Control Network Communication Module

Page 74 of 137

ProSoft Technology, Inc.

November 3, 2008

Upper Layer Status Word

The Upper Layer Status can be set by the CompactLogix processor o the
module. Refer to Upper Layer Status Read Definition (page 92) for more
information.

Bit Message

Description

Value

0 to 11

Error Code (User Defined)

0x0001

12

reserved

0x1000

Bit 15 = 1

Bit 15 = 0

13

1=Warning, 0=No Warning

The upper layer
program is running with
an error but both cyclic
data and message data
are guaranteed.

The upper layer
program is at a stop
with an error but both
cyclic data and
message data are
guaranteed.

0x2000

14

1=Alarm, 0=No Alarm

Both cyclic data and
message data are not
guaranteed.

Both cyclic data and
message data are not
guaranteed.

0x4000

15 1=Run,

0=Stop

Run

Stop

0x8000