Implementation of fl-net – ProSoft Technology MVI69-FLN User Manual
Page 89

Reference MVI69-FLN
♦ CompactLogix Platform
FA Control Network Communication Module
ProSoft Technology, Inc.
Page 89 of 137
November 3, 2008
3.3
Implementation of FL-net
The following two classes are defined considering differences among necessities
of FL-net transmission functions for various devices.
Class Cyclic transmission
Message transmission
Class
Sending
Receiving
Client function
Server function
1 Mandatory
Mandatory
Optional
Optional
2 Not
applicable
Optional Optional
Optional
Notes:
1 "Sending "of "cyclic transmission" indicates a function that the node allocates
common memory and that it transmits data in the common memory of the
own node to other nodes cyclically.
2 "Receiving "of "cyclic transmission" indicates a function that the system
receives data from the common memory of other nodes cyclically.
3 The "client function" of "message transmission" indicates a function that the
node transmits request messages and that it receives response messages.
4 The "server function" of "message transmission" indicates that the node
processes request messages and that it returns response messages.
3.3.1 Information
Tables
Types of management table
Node status management is divided into self-node management table,
participating node management table, and network management table.
1 The self-node management table manages the settings of the self-node.
2 The participating node management table manages the information of the
nodes of in-ring the network.
3 The network management table manages the common network information.
The MVI69-FLN module conforms to the mandatory items in the following tables.
For more information refer to Status Data.
Table name
Information
Conforming level
Node number
Mandatory
Area 1 data top address
Optional (Supported)
Area 1 data size
Optional (Supported)
Area 2 data top address
Optional (Supported)
Area 2 data size
Optional (Supported)
Upper layer status
Mandatory
Token watchdog time
Optional (Supported)
Allowable minimum frame interval time Optional (Supported)
Vendor code
Optional
Manufacturer model name
Optional (Supported: Vendor Model)
Node name
Optional (Supported)
Protocol type
Optional (Supported)
FA link status
Mandatory (Supported)
Own-node
management
Table
Own-node status
Mandatory (Supported)