beautypg.com

System requirements, System, Requirements – ProSoft Technology MVI69-FLN User Manual

Page 10

background image

MVI69-FLN ♦ CompactLogix Platform

Start Here

FA Control Network Communication Module

Page 10 of 137

ProSoft Technology, Inc.

November 3, 2008

For this example, the MVI69-FLN node address is 40, and the FL/ET-T-V2
module node address is 10.

1.1 System

Requirements

The MVI69-FLN module requires the following minimum hardware and software
components:

ƒ Rockwell Automation CompactLogix or MicroLogix processor, with

compatible power supply and one free slot in the rack, for the MVI69-FLN
module. The module requires 800mA of available power.

Important: The MVI69-FLN module has a power supply distance rating of 2 (L43 and L45
installations on first 2 slots of 1769 bus).
Important: For 1769-L23x processors, please make note of the following limitations.
ƒ

1769-L23-QBFC1B = 800mA at 5Vdc (1 MVI69-FLN will use all 800mA of available power. No
other modules can be used with an MVI69 module connected to this processor).

ƒ

1769-L23E-QB1B = 1000mA at 5Vdc (1 MVI69-FLN will use 800mA of available power. One
other module can be used on this rack provided it consumes less than 200mA at 5Vdc.

ƒ

1769-L23E-QBFC1B = 450mA at 5Vdc (no MVI69 module can be used with this processor)

ƒ Rockwell Automation RSLogix 5000 (CompactLogix) or RSLogix 500

(MicroLogix) programming software

ƒ Rockwell Automation RSLinx communication software
ƒ Pentium® II 450 MHz minimum. Pentium III 733 MHz (or better)

recommended

ƒ Supported operating systems:

o

Microsoft Windows XP Professional with Service Pack 1 or 2

o

Microsoft Windows 2000 Professional with Service Pack 1, 2, or 3

o

Microsoft Windows Server 2003

ƒ 128 Mbytes of RAM minimum, 256 Mbytes of RAM recommended