beautypg.com

1769 programmable controller functionality, Requirements – ProSoft Technology ILX69-PBM User Manual

Page 9

background image

ILX69-PBM ♦ CompactLogix or MicroLogix Platform

Contents

PROFIBUS Master Communication Module

User Manual

ProSoft Technology, Inc.

Page 9 of 124

February 4, 2015

1.4

1769 Programmable Controller Functionality

PROFIBUS DP supports acyclic services through messages. These PROFIBUS DP
services are supported by the Studio 5000 programming tool using CIP messages. Not all of
the 1769 programmable controllers support CIP messaging.

The basic PROFIBUS DP acyclic services Global Control or slave Diagnostics request are
also executable in addition to the CIP method by using the I/O area. The following table
displays the 1769 programmable controllers and the functionalities they support.

CompactLogix System

Processor

I/O (cyclic)

CIP
Messaging
(acyclic)

CompactLogix™ 1769-L23

Yes

Yes

CompactLogix™ 1769-L30

Yes

No

CompactLogix™ 1769-L31

Yes

Yes

CompactLogix™ 1769-L32E

Yes

Yes

CompactLogix™ 1769-L35E

Yes

Yes

CompactLogix™ 1769-L36ERM

Yes

Yes


Yes = Functionality supported

No = Functionality not supported

1.5

Requirements

1.5.1 Software Requirements

The software requirements for using the ILX69-

PBM within a CompactLogix™ system are

listed below. You must have the following software installed on your PC unless otherwise
noted:

CompactLogix System
 Studio 5000 programming software, V21.00 or higher

RSLogix™ 5000 programming software, V20.00 or higher


ProSoft Configuration Software
ProSoft fdt Configuration Manager for Rockwell Interfaces V1.0.x.x or higher