ProSoft Technology ILX69-PBM User Manual
Page 71

ILX69-PBM ♦ CompactLogix or MicroLogix Platform
Contents
PROFIBUS Master Communication Module
User Manual
ProSoft Technology, Inc.
Page 71 of 124
February 4, 2015
GLOBAL-BITS
Bit
Offset
Member
Name
Data
Type
Signification
Meaning if Bit is set
0
Ctrl
BOOL
CONTROL-ERROR
Parameterization error
1
Aclr
BOOL
AUTO-CLEAR-ERROR
Module stopped communication with all
slaves and reached the auto-clear-end
state.
2
Nexc
BOOL
NON-EXCHANGE-ERROR
At least one slave has not reached the
data exchange state and no process data
will be exchanged.
3
Fat
BOOL
FATAL-ERROR
Because of major bus error, no further bus
communication is possible.
4
Eve
BOOL
EVENT-ERROR
The module has detected bus short
circuits. The number of detected events is
contained in the Bus_error_cnt variable.
This bit is set when the first event was
detected and will remain set.
5
NRdy
BOOL
HOST-NOT-READY-
NOTIFICATION
Indicates if the Application program has
set its state to operative or not. If this bit is
set the Application program is not ready to
communicate
6
Tout
BOOL
TIMEOUT-ERROR
The module has detected an overstepped
timeout supervision value because of
rejected PROFIBUS telegrams. It is an
indication for bus short circuits while the
master interrupts the communication. The
number of detected timeouts is available in
the Time_out_cnt variable. This bit will be
set when the first timeout is detected and
will remain set.
7
Reserved1
BOOL
Reserved
Reserved, set to 0
Byte
Offset
Structure
Member
Data
Type
Description
24 to 39 Sl_cfg[16]
SINT(16)
List of Configured Slaves (Bit Field)
40 to 55 Sl_state[16]
SINT(16)
List of Activated Slaves (Bit Field)
56 to 71 Sl_diag[16]
SINT(16)
List of Faulted Slaves (Bit Field)