ProSoft Technology ILX69-PBM User Manual
Page 107

ILX69-PBM ♦ CompactLogix or MicroLogix Platform
Contents
PROFIBUS Master Communication Module
User Manual
ProSoft Technology, Inc.
Page 107 of 124
February 4, 2015
7.2.2 ILX69-PBM LEDs
The ILX69-PBM LEDs indicate the status information. Each LED has a specific function
during Run, configuration download, and error indications. The table below shows the
activity of each.
Power On
The PWR LED is described below.
LED
Color
State
Description
PWR
LED green
(Green)
On
Power supply for the device is on
(Off)
Off
Power supply for the device is missing
PROFIBUS System Status
The SYS PROFIBUS network status LED is described below.
LED
Color
State
Description
SYS
Duo LED yellow/green
(Green)
On
Operating system running
(Green/Yellow)
Blinking
Green/Yello
w
Second stage bootloader is waiting for firmware
(Yellow)
Static
Bootloader netX (= romloader) is waiting for second stage
bootloader
(Off)
Off
Power supply for the device is missing or hardware defect
Communication Status
The ILX69-PBM PROFIBUS DP COM LED status is described below.
LED
Color
State
Description
COM
Duo LED red/green
(Green)
On
Communication to all slaves is established
(Green)
Flashing cyclic
PROFIBUS is configured, but bus communication is not
yet released from the application
(Green)
Flashing acyclic
No configuration or faulty configuration
(Red)
Flashing cyclic
Communication to at least one slave is disconnected.
(Red)
On
Communication to all slaves is disconnected or another
serious error has occurred.
Redundant Mode: The active master was not found.