ProSoft Technology ILX69-PBM User Manual
Page 85

ILX69-PBM ♦ CompactLogix or MicroLogix Platform
Contents
PROFIBUS Master Communication Module
User Manual
ProSoft Technology, Inc.
Page 85 of 124
February 4, 2015
Group Select
The Group Select parameter allows the user program to select which of the 8 possible slave
groups is addressed by this service. This command is activated in the slave when the AND
linkage between its internal Group_Ident and the desired Group_Select logic result in a '1'.
The Group_Ident parameter is configured by the master during the startup phase.
If the Group_Ident
parameter is set to a value of ‘0’, the slave does not carry out a group
evaluation (AND linkage) with the received command.
ILX69PBM.CONTROL.SlaveControl.SetSlaveControl_MSG.Response.
Parameter
Data Type
Value
Description
Status
DINT
0x0000
ILX69-PBM Status
Command
DINT
0x2221
Command code
6.3.3 DPV1 Messaging
This section describes DPV1 messaging functions supported by the ILX69-PBM.
Important: Do not configure DPV1 services if your controller does not
allow CIP messaging.
DPV1 Read Command
The MSG instruction format of a DPV1 read command and response is as follows.
ILX69PBM.CONTROL.DPV1.Read.Request
Parameter Data Type Value
Description
.Status
DINT
0x0000
ILX69-PBM Status
.Command
DINT
0x2210
Command code
.SlaveAddres
s
SINT
0 to 125
Slave address
.SlotNumber
SINT
0 to 255
Requested slot
.Index
SINT
0 to 255
Requested index
.Length
SINT
0 to 240
Requested length