ILX69-PBM ♦ CompactLogix or MicroLogix Platform

Contents

PROFIBUS Master Communication Module

User Manual

ProSoft Technology, Inc.

Page 33 of 124

February 4, 2015


 Input Size

– The input size must be at least 88 Bytes (44 Words). It must be large

enough to accommodate the status information required by the module, which is 88
Bytes (44 Words) and the total number of PROFIBUS input data values from the slaves
in the network. You can increase the size of this area using the size of each Input
module connected. The Input image starts with byte 88.

 Output Size

– The output size must be at least 16 Bytes (8 Words). It must be large

enough to accommodate the command information required by the module, which is 16
bytes (8 Words), and the total number of PROFIBUS output data values to the slaves in
the network. You can increase the size of this area using the size of each Output module
connected. The Output image starts with byte 16.

6 Select Next >> or OK for the next configuration dialog.

5.1.3 Module Properties 2

The Requested Packet Interval RPI is shown in the following dialog. Within this time interval,
the I/O data between module and controller are exchanged.

1 Edit the R

EQUESTED

P

ACKET

I

NTERVAL

(RPI) value, if needed.


It is not possible to change the RPI in this dialog separately for each module. The RPI
can be changed in the properties dialog of the "CompactBus Local" for all I/O modules.

2 Click Finish>>
3 Save the project.