6.3.4 CIP Message Error Codes

This section includes error codes and conditions that can occur when using CIP messages.

Your application can be constructed in a manner in which it catches the two possible error
cases:
 CIP Message instruction failure
 The requested command returns an error in its request confirmation

General CIP Message Error Codes

Below are general CIP Message error codes.

Note: Some CIP error codes are public and can also be generated by the
controller.

CIP
Status

Extended
Status

Meaning

Cause

Help

02 hex

00CA hex

Resources unavailable
Out of segments

System has no
segments left to
execute the command

02 hex

03E8 hex

Resources unavailable
Out of CIP com buffer

System has no CIP
communication buffer
left to execute the
command

Check the number of parallel
CIP messages sent to the
module. The module can
process 5 CIP messages in
parallel. Note that RSLinx
can already consume 2 of
these CIP com buffers if the
online browser is active.

02 hex

0519 hex

Resources unavailable
Out of command buffer

System has no
command buffer left to
execute the command

Contact technical support

08 hex

0000 hex

Service not supported

The service code of the
requested object is not
supported

Check parameter of the CIP
Message

14 hex

0000 hex

Attribute not supported

The attribute of the
requested object is not
supported

Check parameter of the CIP
Message

13 hex

0000 hex

Insufficient data

Too little data was
transferred with the
CIP Message

Check the "Source Length"
parameter of the CIP
Message and check the
consistency of all length
parameters within the
requested command.