6.3.4 CIP Message Error Codes
This section includes error codes and conditions that can occur when using CIP messages.
Your application can be constructed in a manner in which it catches the two possible error
cases:
CIP Message instruction failure
The requested command returns an error in its request confirmation
General CIP Message Error Codes
Below are general CIP Message error codes.
Note: Some CIP error codes are public and can also be generated by the
controller.
CIP
Status
Extended
Status
Meaning
Cause
Help
02 hex
00CA hex
Resources unavailable
Out of segments
System has no
segments left to
execute the command
02 hex
03E8 hex
Resources unavailable
Out of CIP com buffer
System has no CIP
communication buffer
left to execute the
command
Check the number of parallel
CIP messages sent to the
module. The module can
process 5 CIP messages in
parallel. Note that RSLinx
can already consume 2 of
these CIP com buffers if the
online browser is active.
02 hex
0519 hex
Resources unavailable
Out of command buffer
System has no
command buffer left to
execute the command
Contact technical support
08 hex
0000 hex
Service not supported
The service code of the
requested object is not
supported
Check parameter of the CIP
Message
14 hex
0000 hex
Attribute not supported
The attribute of the
requested object is not
supported
Check parameter of the CIP
Message
13 hex
0000 hex
Insufficient data
Too little data was
transferred with the
CIP Message
Check the "Source Length"
parameter of the CIP
Message and check the
consistency of all length
parameters within the
requested command.