ProSoft Technology ILX69-PBM User Manual
Page 75

ILX69-PBM ♦ CompactLogix or MicroLogix Platform
Contents
PROFIBUS Master Communication Module
User Manual
ProSoft Technology, Inc.
Page 75 of 124
February 4, 2015
Station Status_3
Slave device status information (continued)
Bit
Offset
Member
Name
Data
Type
Description
0 to 6
Reserved0..6
BOOL
Reserved, set to 0
7
ExtDiagOverflow
BOOL
Slave has a large amount of diagnostics data and cannot send it
all at once
DPV1 Alarm Indication
Bytes 80 to 87 contain the DPV1 Alarm Indication registers. These registers provide
incoming alarm indication data required to respond to a DPV1 alarm that originates from a
slave.
Byte
Offset
Member
Name
Data
Type
Description
80
Alarm_Status
SINT
Status of Alarm Pending, see table below
81
AlarmCnt
SINT
Alarm Counter
82
Rem_Add
SINT
Address of slave with Alarm (0 to 126)
83
Slot_Number
SINT
Slot Number (0 to 254)
84
Seq_Nr
SINT
Sequence Number (0 to 31)
85
Alarm_Type
SINT
Alarm Type (1 to 6, 32 to 126)
86
Alarm_Spec
SINT
Alarm Specification (0 to 7)
87
Reserved
SINT
Reserved, set to 0
Alarm_Status
Bit
Offset
Member
Name
Data
Type
Description
0
AlarmInd
BOOL
Alarm Indication
1
Reserved
BOOL
Reserved, set to 0
2
Reserved
BOOL
Reserved, set to 0
3
Reserved
BOOL
Reserved, set to 0
4
Reserved
BOOL
Reserved, set to 0
5
Reserved
BOOL
Reserved, set to 0
6
Reserved
BOOL
Reserved, set to 0
7
AlarmOverrun
BOOL
Alarm Overrun