beautypg.com

Fault diagnosis – Emerson MPR15 Series User Manual

Page 79

background image

Maintenance 79

25A Switch Mode Rectifier

NT5C06B / C Installation and User Manual

Fault diagnosis

Symptom:

Possible cause

Low Voltage Test/Bypass
LED lit

The switch is on the Test/Bypass position

LVA and LVD LED lit

Check the voltage level at the test jacks and

the position of the Test switch. Verify the LVA

and LVD adjustment. Set the test switch to the

Test/Bypass position to verify their operation.

Replace the circuit pack if it is still not

operational.

The LVD disconnects the load

Verify the voltage at the test jacks. Remove the

faceplate and check the fuse located on the

control PCB.