104 Appendix A: NT5C10BF-1 and NT5C10BP

UM5C06B / C ( 169-2071-500 ) P0711722 Standard 10.00 May 2001

General requirements

Power shelf size

The NT5C10BF-1 and NT5C10BP power shelves are designed specifically

for the FTIP/FTOP application. They measure 17.0 inches W x 7.0 inches H

x 12.0 inches D. They provide housing for up to three MPR25EX

(NT5C06BB) SMRs (FTOP application), or two MPR15E (NT5C06CB/CD)

SMRs plus one 50 A LVD module (NT6C13FA) (FTIP application). The

middle rectifier is wired as Standby.

Shelf labeling

The following component and connection positions are labeled on the

power shelf:

a) Front (left to right):

- MAIN1
- STANDBY
- MAIN2/LVD

b) Rear (right to left):

Signal Connections:

- RC-

TB1-1

- RG+

TB1-2

- J1

TB1-3

- J2

TB1-4

- RFA

TB1-5

- NSR

TB1-6

Power Connections:

- RTNA

TB2-1

- -48V A

TB2-2

Note:

The Standby rectifier HVSD should be adjusted 0.5

higher than the main rectifier(s) and its float voltage

should be adjusted 0.1 volts lower than the main

rectifier(s).