Technical specifications, Warning – Emerson MPR15 Series User Manual
Page 106
106 Appendix B: NT5C10CO shelf
UM5C06B / C ( 169-2071-500 ) P0711722 Standard 10.00 May 2001
Technical specifications
WARNING
The power shelf must be connected to 120 V AC and a
20-ampere circuit. The AC receptacle must be rated 20
amperes and wired with #12 AWG. Non-conformance to
these requirement may cause the AC breaker/fuse at the
AC distribution cabinet to open, under certain operational
conditions, resulting in loss of power for both rectifiers.
Input AC:
120 V AC/18 A
Power system maximum load:
6 A typical to 10 A maximum.
Battery charging current:
7 to 11 A, depending on power system
load.
Maximum battery reserve:
120 AH (based on 8 hours).
Delayed Start delay:
Two positions; 12 and 24 hours (12
hours for 6 A load application and 24
hours for 10 A load applications).
Factory delayed start setting: 24 hours
6
5
4
3
2
1
OPEN
CLOSED
6
5
4
3
2
1
OPEN
CLOSED
6
5
4
3
2
1
OPEN
CLOSED
24 hours
Delay
12 hours
Delay
30 seconds
(test)
Delay
Test Mode:
Two switches are provided. One to reset the timer without
interrupting the AC and one to reduce the starting delay to
less than one minute.