106 Appendix B: NT5C10CO shelf

UM5C06B / C ( 169-2071-500 ) P0711722 Standard 10.00 May 2001

Technical specifications

WARNING

The power shelf must be connected to 120 V AC and a

20-ampere circuit. The AC receptacle must be rated 20

amperes and wired with #12 AWG. Non-conformance to

these requirement may cause the AC breaker/fuse at the

AC distribution cabinet to open, under certain operational

conditions, resulting in loss of power for both rectifiers.

Input AC:

120 V AC/18 A

Power system maximum load:

6 A typical to 10 A maximum.

Battery charging current:

7 to 11 A, depending on power system

load.

Maximum battery reserve:

120 AH (based on 8 hours).

Delayed Start delay:

Two positions; 12 and 24 hours (12

hours for 6 A load application and 24

hours for 10 A load applications).

Factory delayed start setting: 24 hours

6

5

4

3

2

1

OPEN

CLOSED

6

5

4

3

2

1

OPEN

CLOSED

6

5

4

3

2

1

OPEN

CLOSED

24 hours
Delay

12 hours
Delay

30 seconds
(test)
Delay

Test Mode:

Two switches are provided. One to reset the timer without
interrupting the AC and one to reduce the starting delay to
less than one minute.