Start-up procedure factory set voltage limits – Emerson MPR15 Series User Manual
Page 60
60 Installation and start-up procedures
UM5C06B / C ( 169-2071-500 ) P0711722 Standard 10.00 May 2001
Figure 23 - Embedded shelf - LVD connections - side access
Start-up procedure
Factory set voltage limits
All rectifiers are factory set as follows unless otherwise requested by the
customer:
MPR15 MPR25
Float Voltage:
52.10 V DC
48.00 V DC
Equalize:
0.70 V DC above float 0.00 V DC above float
HVSD:
59.00 V DC
56.50 V DC
LVD/LVD Alarms
Low Voltage Alarm (LVA):
47.00 V DC
Low Voltage Disconnect (LVD):
43.50 V DC
2
1
8
CHASSIS
GROUND
BAT SENSE
LEADS
TO LOAD
[T]
[B]
BAT
LOAD
BAT RTN