60 Installation and start-up procedures

UM5C06B / C ( 169-2071-500 ) P0711722 Standard 10.00 May 2001

Figure 23 - Embedded shelf - LVD connections - side access

Start-up procedure

Factory set voltage limits

All rectifiers are factory set as follows unless otherwise requested by the

customer:

MPR15 MPR25

Float Voltage:

52.10 V DC

48.00 V DC

Equalize:

0.70 V DC above float 0.00 V DC above float

HVSD:

59.00 V DC

56.50 V DC

LVD/LVD Alarms
Low Voltage Alarm (LVA):

47.00 V DC

Low Voltage Disconnect (LVD):

43.50 V DC