Appendix B: NT5C10CO shelf 111

25A Switch Mode Rectifier

NT5C06B / C Installation and User Manual

The above settings will provide a delay of approximately 24 hours, which is

sufficient to charge the batteries with a reserve of 80 to 120AH and at the

same time supply power to a 10 A load. When the load is 6 A, or less on a

battery reserve of less than 80AH, open SW1-4 and close SW1-3 for a delay

of 12 hours.

Troubleshooting

The following are recommended steps for analyzing possible malfunctions of

a system equipped with an NT5C10CO power shelf. This is in addition to

the information contained in the “Troubleshooting” section of User Manual

(UM) 167-9021-107.

Table 13 - Systems equipped with NT5C10CO power shelf fault diagnosis

Fault symptom

Possible causes

Delayed Start did not

activate (delayed start

LED is not lit):

No ACV at the power shelf input terminals.

Main rectifier has been removed or generates an RFA.

Faulty circuit pack.

Incorrect time delay:

Verify that the SW1 switch is properly set.

Faulty circuit pack.

—end—