beautypg.com

Lvd installation in the shelf – Emerson MPR15 Series User Manual

Page 59

background image

Installation and start-up procedures 59

25A Switch Mode Rectifier

NT5C06B / C Installation and User Manual

LVD installation in the shelf

The LVD is installed in the right hand shelf position as describes in

Procedure 10.

Procedure 10 - LVD installation in the shelf

Step Action

1

Release the clamping bar and blank panel (see Procedure 1).

2

Remove the LVD faceplate.

3

Slide the LVD about two thirds of the way into the shelf.

4

Connect the LVD as shown in Figure 22 and 23. (Use 2 X 10 AWG wires
for contactors).

5

Re-install the small LVD faceplate.

6

Push the LVD the remaining distance into the shelf and slide the blank
panel into the shelf between the LVD and the adjacent rectifier.

7

Secure the clamping bar by tightening the two captive screws.

end

Figure 22 - Embedded shelf - LVD connections - rear access

2

1

8

CHASSIS

GROUND

BAT SENSE

LEADS

TO LOAD

[T]

[B]

BAT

LOAD

BAT RTN

This manual is related to the following products: