Emerson MPR15 Series User Manual
Page 44
44 Installation and start-up procedures
UM5C06B / C ( 169-2071-500 ) P0711722 Standard 10.00 May 2001
Shelf configuration
19-inch system shelf (NT5C10CA-1/2)
Capacity:
-2 x MPR25
AC common cable: 2/8 AWG armored cable Reference Figure 13 (side)
DC cables:
6 AWG (BAT and BAT RTN) Ref. Figure 19 (side)
Figure 20 (rear)
Signals 2 x 8 conductor cables terminated with connectors.
19-inch embedded shelf (NT5C10BF-1 and NT5C10BP)
Capacity:
- 3 x MPR25
AC common cable
- 2/6 AWG Armored Cable
DC cables
- 6 AWG (BAT and BAT RTN)
Signals:
- one cable (for remote sensing and alarm)
Note:
See Appendix A for additional information
.
19-inch embedded shelf (NT5C10BA-1/2)
Capacity:
-
1 x MPR25 + LVD
-
1 x MPR25 + 1 x MPR25 standby + LVD
AC common cable
-
2/8 AWG armored cable. Refer to Figure 13
(Side)
DC cables
-
6 AWG (BAT and BAT RTN). Refer to
Figure 19 (Side) and Figure 20
(Rear)
Signals:
-
1 cable (for remote sensing and alarm).
19-inch embedded shelf (NT5C10BA-3/4)
Capacity:
-
2 x MPR25
AC individual cable:
-
2/12 AWG armored cable. Refer to Figure 15
DC cables:
-
6 AWG (BAT and BAT RTN). Refer to
Figure 19
(side) and to Figure 20 (rear)
Signals:
-