46 Installation and start-up procedures
UM5C06B / C ( 169-2071-500 ) P0711722 Standard 10.00 May 2001
23-inch embedded shelf (NT5C10BC-3, NT5C10BD-3)
Capacity:
- 3 x MPR25
AC common cable:
- 2/6 AWG armored cable. Refer to Figure 13
(Side)
DC cables:
- 4 AWG (BAT and BAT RTN). Refer to Figure 19
(side) and to Figure 20
(rear)
Signals:
- 1 cable (for remote sensing and alarm)
23-inch embedded shelf (NT5C10BM)
Capacity:
- 3 x MPR25
AC common cable:
- 2/6 AWG armored cable. Refer to Figure 13 (side)
DC cables
- 4 AWG (BAT and BAT RTN). Refer to Figure 19
(side) and to Figure 20 (rear)
Signals:
- 1 cable (for remote sensing and alarm)
23-inch embedded shelf (NT5C10BL)
Capacity:
- 3 x MPR25
AC individual cable
- 2/12 AWG armored cable. Refer to Figure 16
DC cables
- 4 AWG (BAT and BAT RTN). Refer to Figure 19
(side) and to Figure 20 (rear)
Signals:
- 1 cable (for remote sensing and alarm)
23-inch embedded shelf (NT5C10BJ, NT5C10BK)
Capacity:
- 2x MPR25
AC common cable
- 2/8 AWG armored cable. Refer to Figure 13
(Side)
DC cables
- 6 AWG (BAT and BAT RTN). Refer to Figure 19
(side) and to Figure 20 (rear)
Signals:
- 2 cables (for remote sensing and alarm)