25A Switch Mode Rectifier

NT5C06B / C Installation and User Manual

Maintenance

Maintenance

Rectifier

Procedure 20 - Float/equalize and remote equalize

Step Action

1

Disconnect the sense leads from the rectifier, by either disconnecting a

quick disconnect tab TB1 on the shelf or removing the appropriate

system fuse. (See the “Introduction” chapter for system applications.)

2

Open the output DC breaker. The unit is ready for local adjustment.

3

The unit should provide voltage to the front panel test point terminals. If

it does not, cycle the AC breaker to reset the unit.

4

Momentarily hold the FLT/EQL switch to EQL for local equalize.

5

Using a voltmeter, verify and adjust the EQL potentiometer to obtain an

output voltage reading of 0.5 volts (see Note below) above the system

equalize requirement.

6

Release the FLT/EQL switch. Verify that the output voltage drops to the

float value plus 0.5V (see Note below).

7

Verify the HVSD level. It is recommended that it be set approximately 3 V

above the shutdown limit of the power system. Refer to the “Installation

and start-up procedure” chapter, subsection “Start-up procedure”, for the

verification procedure.

8

Reconnect the sense leads locally to the rectifier. Close the output DC

breaker. Cycle the AC breaker to reset the unit. The RFA/ON LED should

be green.

–end–

Note:

The 0.5 volt DC extra does not apply to MPR25 rectifiers

above Release 30.