Installation and start-up procedures 43

25A Switch Mode Rectifier

NT5C06B / C Installation and User Manual

Figure 12 - 19-inch power shelf (NT5C10BF and NT5C10BP only)

Cabling the power shelf

The AC and DC cabling size and routing inside the shelf are determined by

the following shelf configurations. Refer to Figures 13 to 20 for routing.

Note:

The grounding of the shelf is provided by the AC

armored cable ground wire attached to a two-hole ground

lug located on the inside wall of the shelf chassis. The

shelf is also grounded to the rack or cabinet frame by one

of the shelf mounting screws which is installed with an

external tooth washer. This grounding method is

sufficient but if desired, an extra ground cable (color

green insulation 105°C), of size 8 AWG for common AC,

or 12 AWG for individual AC applications, can be

installed in addition to the existing cable and be

connected to an external system ground. Using a 0.25-

inch ring lug terminal, the new ground wire can be

installed on one of the existing ground lug screws located

inside the shelf. Route the wire along the inside top back

of the shelf and make it exit out of the right DC cabling

side opening. Ensure the wire does not interfere with the

rectifier connections. See Figure 13 for the extra ground

connection mounting location.