Operation 23

25A Switch Mode Rectifier

NT5C06B / C Installation and User Manual

Rectifier failure alarm (RFA)

The rectifier incorporates facilities for monitoring its operational state and

extends a global alarm upon detection of an internal failure or a no load

condition (see Note below). When the rectifier operates in parallel with

other rectifiers and its output voltage is adjusted lower, the RFA LED will

change to RED and an RFA alarm will be sent.

Note:

Give an alarm at no load condition only for the following

releases or under.

NT5C06BB, BB-1, BB-3, BC

Rel. 10

NT5C06CA, CA-1, CA-3, CA-5 ,CC

Rel. 10

NT5C06CB, CB-1, CB-3, CD

Rel. 12

NT5CO6CE-61(-46)

Rel. 12

Fan failure alarm

A fan failure will activate the fan alarm and inhibit the operation of the

rectifier. An RFA will also be issued upon inhibition of the rectifier.

Internal high voltage shut down (HVSD)

The rectifier includes a high voltage monitor. Whenever the rectifier output

voltage exceeds a value adjustable from -52 to -59.5 V it shuts down

immediately, locks out, and transmits an RFA. This function is not

dependent on the output load condition.

Local ON/OFF control (DC and optional AC breakers)

Circuit breakers are used to turn the rectifier ON/OFF locally and

disengage it from the DC circuit. The local OFF control overrides the

remote control signals.

Inrush current limiting fuse (F1)

A 3/4 A, 250 V fuse is connected in line with the soft start circuitry to

protect the input circuitry against high inrush currents in case of an

internal failure. On the MPR15E modes NT5C06CB/CD/CE, failure

of this fuse during operation will disable the unit. See the

“Recommended Replacement Parts” section to order a replacement

fuse.