64 Installation and start-up procedures

UM5C06B / C ( 169-2071-500 ) P0711722 Standard 10.00 May 2001

Parallel verification

Note 1 :

The following does not apply to rectifier shelf

applications with the hot stand-by option. For delayed

start shelf applications, wait after the delay expires before

performing the next step.

Note 2 :

All the rectifiers in the shelf or system must have been

individually adjusted as indicated in the Power up, HVSD

adjustment, FLT adjustment and Equalize adjustment

procedures before proceeding with the following steps.

DANGER

When adding or replacing a rectifier verify that the rectifier

DC and AC circuit breakers are in the OFF position.

Reconnect the sense leads (if disconnected before the rectifier power-up) for

all the shelf rectifiers

by connecting the quick tab of TB-1 on the shelf
or

re-installing the sense fuse (system application)
or

setting the dip switches to the ON position (system application)