28 Operation

UM5C06B / C ( 169-2071-500 ) P0711722 Standard 10.00 May 2001

Local/remote high voltage shutdown reset

The rectifier may be reset from an HVSD condition locally, by resetting the

AC circuit breaker (if so equipped), the associated AC breaker on the

distribution panel, or remotely by applying a ground signal at the HVSDR

input of the rectifier provided:

the 'TR' lead is not activated

the 'AC' (optional) and 'DC' breakers are closed

Remote equalize control

The rectifier is equipped with remote equalize control. This function is

operated by applying a remote ground signal (BAT POS) and returns to

normal (Float) operation upon removal of the signal.

Signal connections

The interface connector located at the rear of the rectifier provides control,

alarm and monitoring signals. The control inputs are activated by a ground

(BAT RTN) signal. The alarm contacts are extended by relays and are

isolated from each other, and from the rectifier chassis. All contacts are rated

60 V DC and 0.5 A.