beautypg.com

Scanner instruction manual – Precision Digital PD6080 User Manual

Page 81

background image

PD6080/PD6081 Super Snooper Modbus

Scanner Instruction Manual

81

Programmable Exponent Function Menu (prog e)

The programmable exponent function is used to calculate open-channel flow measured with a level
transmitter in weirs and flumes. The flow rate is proportional to the head height. Scale the scanner so that
the low input signal (e.g. 4 mA) is equal to zero flow and the high input signal (e.g. 20 mA) is equal to the
maximum flow. This method works well for all weirs and flumes that have a simple exponent in the flow
calculation formula. For weirs and flumes with complex exponents it is necessary to use a strapping table
and the 32-point linearization of the scanner.

SAVED flashes

before moving

to next PV.

This manual is related to the following products: