Connections

All connections are made to removable screw terminal connectors located at the rear of the scanner.

!

Caution!


Use copper wire with 60°C or 60/75°C insulation for all line voltage connections.
Observe all safety regulations. Electrical wiring should be performed in
accordance with all applicable national, state, and local codes to prevent
damage to the scanner and ensure personnel safety.

Connectors Labeling

The connectors’ label, affixed to the scanner, shows the location of all connectors available with
requested configuration.

Warning!

Do not connect any equipment other than Precision Digital’s expansion
modules, cables, or scanners to the RJ45 M-LINK connector. Otherwise
damage will occur to the equipment and the scanner.

Figure 6. Connector Labeling for Fully Loaded PD6080/6081

Power Connections

Power connections are made to a two-terminal connector labeled POWER on the back of the scanner. The
scanner will operate regardless of DC polarity connection. The + and - symbols are only a suggested wiring
convention.

AC or DC

POWER

Required External Fuse:

5 A max, 250 V Slow Blow

POWER

+

-

Figure 7. Power Connections