beautypg.com

Scanner instruction manual – Precision Digital PD6080 User Manual

Page 64

background image

PD6080/PD6081 Super Snooper Modbus

Scanner Instruction Manual

64

Pump Alternation Control Applications (Altern)

For pump control applications where two or more similar pumps are used to control the level of a tank or a
well, it is desirable to have all the pumps operate alternately. This prevents excessive wear and
overheating of one pump over the lack of use of the other pumps.
Up to 8 relays can be set up to alternate every time an on/off pump cycle is completed. The set points
and reset points can be programmed, so that the first pump on is the first pump off.

Application #1: Pump Alternation Using Relays 1 & 2

1. Relays 1 and 2 are set up for pump alternation.
2. Relays 3 and 4 are set up for low and high alarm indication.


Set and Reset Point Programming with Pump Alternation

Relay

Set Point

Reset Point

Function

1

30.000

10.000

Controls pump 1 & 2

2

35.000

5.000

Sets dual pump trigger

3 4.000 9.000

Controls

low

alarm

4

40.000

29.000

Controls high alarm


Pump Alternation Operation

1. Pump #1 turns on when the level reaches 30.000, when level drops below 10.000 pump #1 turns off.
2. The next time the level reaches 30.000, pump #2 turns on, when the level drops below 10.000, pump

#2 turns off.

3. If the level doesn’t reach 35.000 pump #1 and pump #2 will be operating alternately.
4. If pump #1 cannot keep the level below 35.000 pump #2 will turn on at 35.000, then as the level drops

to 10.000 pump #1 turns off, pump #2 is still running and shuts off below 5.000.

5. Notice that with the set and reset points of pump #2 outside the range of pump #1, the first pump on

is the first pump to go off. This is true for up to 8 alternating pumps, if set up accordingly.

6. Relay #3 will go into alarm if the level drops below 4.000 and relay #4 will go into alarm if the level

exceeds 40.000.

7. Adding the 4 external relays expansion module allows using the 4 SPDT internal relays for pump

alternation and the 4 SPST external relays for high, high-high, low, and low-low alarm indication.

This manual is related to the following products: