Scanner instruction manual, Display parameter action/setting description – Precision Digital PD6080 User Manual
Page 29

PD6080/PD6081 Super Snooper Modbus
Scanner Instruction Manual
29
Display
Parameter
Action/Setting Description
DLY 1*
Delay 1*
*Enter relay 1-8 time delay setup
On 1
On 1
Set relay 1 On time delay
OFF 1
Off 1
Set relay 1 Off time delay
break
Break
Set relay condition if communication break detected
No act
No action
Ignore break condition. No change in relay state when
Communications Break detected.
On
On
Relay goes to alarm condition when break detected. Relay turns on
when Communications Break detected.
Off
Off
Relay goes to non-alarm condition when break detected. Relay turns
off when Communications Break detected.
Aout
Analog output
Enter the Analog Output scaling menu
AOut 1*
Aout channel
Analog Output source channel (*1-3)
Dis 1
Display 1
Program the first Display value for the Analog Output.
Out 1
Output 1
Program the first Output value that corresponds to the Display 1 value
for the Analog Output. (e.g. 4.000 mA).
Dis 2
Display 2
Program the second Display value for the Analog Output.
Out 2
Output 2
Program the second Output value that corresponds to the Display 2
value for the Analog Output. (e.g. 4.000 mA). (e.g. 20.000 mA)
serial
Serial
Enter Serial menu
SCan.ID
Scan ID
Enter Scan ID of the meter being polled (1-247)
baud
Baud Rate
Select Baud Rate (Choices: 300/600/1200/2400/4800/9600/19,200)
(Must match that of other devices)
Tr dly
Transmit Delay
Enter Transmit Delay
(Master’s delay must be greater than Snooper or slave devices)
parity
Parity
Select Parity (Even, Odd, None 1-Stop, or None 2-Stop)
(Must match that of other devices)
t-byt
Byte-to-byte Timeout
Enter the timeout value allowed between received bytes.
(This is used to fix communication problems with slow devices).
pass
Password
Enter the Password menu
Pass 1
Password 1
Set or enter Password 1
Pass 2
Password 2
Set or enter Password 2
Pass 3
Password 3
Set or enter Password 3
unloc
Unlocked
Program password to lock scanner
locd
Locked
Enter password to unlock scanner
999999
-99999
Flashing
Over/under range condition