Scanner instruction manual, Serial communications, General – Precision Digital PD6080 User Manual
Page 11

PD6080/PD6081 Super Snooper Modbus
Scanner Instruction Manual
11
Serial Communications
SCANNER ID
1 – 247 (Scanner Modbus address)
BAUD RATE
300 – 19,200 bps
TRANSMIT
TIME DELAY
Programmable 0 to 4999 ms
This is the time the scanner will wait for a slave to respond before sending
another request on the bus. This value should be greater than 100 ms to avoid
collisions on the bus.
DATA
8 bits (1 start bit, 1 or 2 stop bits)
PARITY
Even, Odd, or None with 1 or 2 stop bits
BYTE-TO-BYTE
TIMEOUT
0.01 – 2.54 second
TURN AROUND
DELAY
Less than 2 ms (fixed)
Note: Refer to the P
RO
V
U
®
Scanner Modbus Register Tables located at www.predig.com.
General
INPUT/OUTPUT
Modbus RTU over RS-485, Two analog inputs (4-20 mA,
±10 V)
DISPLAY
Upper display: 0.60" (15 mm) high, red LEDs
Lower display: 0.46" (12 mm) high, red LEDs
6 digits each (-99999 to 999999), with lead zero blanking
DISPLAY
INTENSITY
Eight user selectable intensity levels
OVERRANGE
Values greater than 999999 cause the display to flash 999999
UNDERRANGE
Values less than -99999 cause the display to flash -99999
PROGRAMMING
METHODS
Four front panel buttons, digital inputs, PC and ScanView software, Modbus
registers, or cloning using Copy function.
MAX/MIN
DISPLAY
Max/min readings are stored until reset by the user or when power to the
scanner is turned off. User can reset by front panel pushbuttons, digital input, or
via Modbus registers.
PASSWORD
Three programmable passwords restrict modification of programmed settings.
Pass 1: Allows use of function keys and digital inputs
Pass 2: Allows use of function keys, digital inputs and editing set/reset points
Pass 3: Restricts all programming, function keys, and digital inputs.
F4 DIGITAL INPUT
CONTACTS
50k ohm pull-up to 3.3 VDC.
Connect normally open contacts across F4 to COM.
F4 DIGITAL INPUT
LOGIC LEVELS
Logic High: 3 to 5 VDC
Logic Low: 0 to 1.25 VDC
NON-VOLATILE
MEMORY
All programmed settings are stored in non-volatile memory for a minimum of
ten years, with or without power.
POWER
OPTIONS
85-265 VAC 50/60 Hz, 90-265 VDC, 20 W max
or jumper selectable 12/24 VDC
± 10%, 15 W max
FUSE
Required external fuse: UL Recognized, 5 A max, slow blow; up to 6 scanners
may share one 5 A fuse
ISOLATED
TRANSMITTER
POWER SUPPLY
Terminals P+ & P- : 24 VDC
± 10%.
Selectable for 24, 10, or 5 VDC supply (internal jumper J4).
ProVu Series (PD6080/81): 85-265 VAC models rated @ 200 mA max, 12/24 VDC
powered models rated @ 100 mA max, 5 or 10 VDC supply rated @ 50 mA max.
ProtEX-MAX (PD8 Series): All models transmitter supply rated @ 25 mA max.