PD6080/PD6081 Super Snooper Modbus
Scanner Instruction Manual
13
TIME DELAY
0 to 999.9 seconds, on & off relay time delays
Programmable and independent for each relay
FAIL-SAFE
OPERATION
Programmable and independent for each relay.
Note: Relay coil is energized in non-alarm condition.
In case of power failure, relay will go to alarm state.
AUTO
INITIALIZATION
When power is applied to the scanner, relays will reflect the state of the input to
the scanner.
Isolated 4-20 mA Transmitter Output
OUTPUT SOURCE
PV1-16, math channels C1-4, set points 1-8, or manual control mode
SCALING RANGE
1.000 to 23.000 mA for any display range
CALIBRATION
Factory calibrated: 4.000 to 20.000 = 4-20 mA output
ANALOG OUT
PROGRAMMING
23.000 mA maximum for all parameters:
Overrange, underrange, max, min, and break
COMMUNICATIONS
BREAK
Programmable mA output when a slave device does not reply within the
response timeout.
ACCURACY
± 0.1% of span ± 0.004 mA
TEMPERATURE
DRIFT
0.4 µA/
°C max from 0 to 65°C ambient, 0.8 µA/°C max from -40 to 0°C ambient.
Note: Analog output drift is separate from input drift.
ISOLATED
TRANSMITTER
POWER SUPPLY
Terminals I+ & R: 24 VDC
± 10%. May be used to power the 4-20 mA output or
other devices. Refer to Figure 6 on page 19 and Figure 13 on page 23.
ProVu Series (PD6080/6081): All models rated @ 40 mA max.
ProtEX-MAX (PD8 Series): All models @ 25 mA max.
EXTERNAL LOOP
POWER SUPPLY
35 VDC maximum
OUTPUT LOOP
RESISTANCE
Power supply
Minimum
Maximum
24 VDC
10
Ω
700
Ω
35 VDC (external)
100
Ω
1200
Ω
Dual Process Input
TWO INPUTS
Two analog inputs, each separately field selectable:
0-20 mA, 4-20 mA;
±10 V (0-5, 1-5, 0-10 V)
PV ANALOG
CHANNEL ID
Ch-A mA: Assign PV to ID 256 or Ch-A volt: 257;
Ch-B mA: Assign PV to ID 258 or Ch-B volt: 259
ACCURACY
±0.03% of calibrated span ±1 count, square root & programmable exponent
accuracy range: 10-100% of calibrated span
TEMPERATURE
DRIFT
0.005% of calibrated span/
°C max from 0 to 65°C ambient,
0.01% of calibrated span/
°C max from -40 to 0°C ambient
SIGNAL INPUT
CONDITIONING
Linear, square root, programmable exponent, or
round horizontal tank volume calculation
MULTI-POINT
LINEARIZATION
2 to 32 points for PV1 and PV2
PROGRAMMABLE
EXPONENT
1.0001 to 2.9999
LOW-FLOW
CUTOFF
0-999999 (0 disables cutoff function) for PV1 and PV2