Scanner instruction manual, Select menu ( select ) – Precision Digital PD6080 User Manual
Page 78
PD6080/PD6081 Super Snooper Modbus
Scanner Instruction Manual
78
Select Menu (SELect)
The Select menu is used to select the input data linearization function (linear, square root, programmable
exponent, or round horizontal tank), math functions, constants, low-flow cutoff, and analog output
programming. Multi-point linearization is part of the linear function selection.
Input Data Conditioning Function Menu (Functn)
The Function menu is used to select the input-to-output transfer function applied to the input data: linear,
square root, programmable exponent, or round horizontal tank volume calculation. Multi-point
linearization (for PV1 and PV2) is part of the linear function selection. Scanners are set up at the factory
for linear function with 2-point linearization. The linear function provides a display that is linear with
respect to the input data (e.g 0.000 = 0.000, 10.000 = 10.000, and then 5.000 = 5.000).