beautypg.com

Safety information, Installation, Scanner instruction manual – Precision Digital PD6080 User Manual

Page 16: Unpacking, Panel mounting

background image

PD6080/PD6081 Super Snooper Modbus

Scanner Instruction Manual

16

SAFETY INFORMATION

!

CAUTION: Read complete instructions prior to

installation and operation of the scanner.

WARNING: Risk of electric shock or

personal injury.

INSTALLATION

There is no need to remove the scanner from its case to complete the installation, wiring, and setup
of the scanner.

Unpacking

Remove the scanner from box. Inspect the packaging and contents for damage. Report damages, if
any, to the carrier. If any part is missing or the scanner malfunctions, please contact your supplier or
the factory for assistance.

Panel Mounting

• Prepare a standard 1/8 DIN panel cutout – 3.622" x 1.772" (92 mm x 45 mm). Refer to Figure 1 for

more details.

• Clearance: allow at least 6" (152 mm) behind the panel for wiring.
• Panel thickness: 0.04" - 0.25" (1.0 mm - 6.4 mm).

Recommended minimum panel thickness to maintain Type 4X rating: 0.06" (1.5 mm) steel panel,
0.16" (4.1 mm) plastic panel.

• Remove the two mounting brackets provided with the scanner (back-off the two screws so that there is

¼" (6.4 mm) or less through the bracket. Slide the bracket toward the front of the case and remove).

• Insert scanner into the panel cutout.
• Install mounting brackets and tighten the screws against the panel. To achieve a proper seal, tighten

the mounting bracket screws evenly until scanner is snug to the panel along its short side. DO NOT
OVER TIGHTEN, as the rear of the panel may become damaged.

Panel

Gasket

Mounting

Bracket

Mounting

Screw

Removable
Connectors

Figure 1. 1/8 DIN Panel Cutout Dimensions & Panel Mounting Details

Warning!

Hazardous voltages exist within enclosure.
Installation and service should be performed only by trained service
personnel.

3.622" (92 mm)

1.772"

(45mm)

Panel Cutout

to DIN 43700

Square Corners to 0.060"

(1.5mm) Max Radius

A

B

Tolerances:

A: +0.032 (+0.8mm)

-0.000 (-0.0mm)

B: +0.024 (+0.6mm)

-0.000 (-0.0mm)